Requirements for Commercial Type Tents Introduction:
Commercial type tents are tension pole tents normally rented from and erected by a party or tent rental businesses. Typically the tent is larger than 800 sq. ft. (20ft. x 40ft.) in size. The tent may or may not have side coverings. Any type of food preparation (cooking) is prohibited unless done so in a separate tent or area away from other use tents and approved by the State Fire Marshal.
Fire and life safety requirements for tents are designed to comply with Codes and Standards from the National Fire Protection Association (NFPA). NFPA 101, the Life Safety Code (2006 edition), sets minimum requirements which provide for a measure of safety from fire and the requirements for means of emergency egress. The following summarizes the requirements.
Flame Resistance:
All tents shall be flame resistant. All tent fabric shall meet the flame propagation performance criteria contained in NFPA 701. Certificate of flame resistance shall be attached to the tent or otherwise provided to the State Fire Marshal. (NFPA 101 - 11.11.2)
Location and Spacing:
There shall be a minimum of 10 feet between stake lines. (NFPA 101 - 11.11.3.1) Adjacent tents shall provide an area to be used as means of emergency egress. (NFPA 101 - 11.11.3.2) Spacing shall be approved by the State Fire Marshal.
Placement of tents relative to other structures shall be approved by State Fire Marshal, with consideration given to occupancy, use, opening, exposure, and other similar factors. (NFPA 101 - 11.11.3.5)
Fire Hazards:
Ground Within and Near the Tent: This portion of the Code prohibits the use of hay or other combustible material as ground covering. The ground enclosed by any tent, and the ground for a reasonable distance but not less than 10 feet outside of such a tent(s) shall be cleared of all flammable or combustible material or vegetation. (NFPA 101 - 11.11.4.1)
Cigarette Smoking:
Smoking is not permitted within the tent. (NFPA 101 - 11.11.4.2)
Open Flames:
Open flame devices, candles, and cooking are not permitted within tents.
a. Sterno type devices for heating prepared food for serving are permitted.
b. A separate tent (minimum of 10 feet from the dining tent) is preferred to be used for serving prepared food.
c. When food serving is in the dining tent, the serving area shall be a minimum of 10 feet from the nearest dining tables.
Heaters for Cold Weather:
a. Fired Heaters: Only labeled heating devices are permitted. Fuel-fired heaters and their installation shall be approved by the State Fire Marshal.(NFPA 101 - 11.11.6.1.1 & 11.11.6.1.2)
b. Liquefied petroleum gas (LPG) heaters are not permitted unless the tanks are a minimum of 5 feet from any tent. The tanks shall be secured in the upright position, protected from vehicular traffic, and be in accordance with NFPA 58, Liquefied Petroleum Gas Code. LPG heaters and their installation shall be approved by the State Fire Marshal. (NFPA 101 - 11.11.6.1.3 & 11.11.6.1.4).
c. Electric Heaters: Only labeled heaters are permitted. Heaters shall be connected to electricity by electric cable suitable for outside use and is of sufficient size to handle the electrical load. Electric heaters and their installation shall be approved by the State Fire Marshal. (NFPA 101 - 11.11.6.2).
Tents for Dining:
Main aisles and aisle access walkway between tables:
Aisles shall be maintained so any individual is able to move without undue hindrance at any time to the exits. Aisles are also maintained so crowd management, security, and emergency services personnel are able to reach any individual at any time, without undue hindrance. Layouts shall be approved by the State Fire Marshal.
a. Exits shall be located and exit access shall be arranged so exits are readily
accessible at all times. (NFPA 101 - 13.2.1 & 7.5.1.1)
b. Exits shall be arranged so the total length of travel distance from any point to
reach an exit shall not exceed 200 feet. (NFPA 101 - 13.2.6)
c. The maximum travel distance to an aisle is 36 feet. (Maximum length of a row of
tables is 72 feet.) (NFPA 101 - 13.2.5.7.5)
d. The minimum distance between dining tables providing seating on both sides shall be 50 inches from table edge to table edge. The distance allows 19 inches each for seating at each table and 12 inches for walkway. (NFPA 101 - 13.2.5.7)
e. The minimum distance between dining tables providing seating on one side shall be 31 inches from table edge to table edge. This allows 19 inches for the seating and 12 inches of walkway. (NFPA 101 - 13.2.5.7)
f. The main center walkway aisle shall be a minimum of 44 inches of clear width. (NFPA 101 - 13.2.5.8.2)
Tents for Merchandise Display or Sales:
No display or exhibit shall be installed or operated to interfere in any way with access to any exit.
a. Exits shall be located and exit access shall be arranged so exits are readily accessible at all times. (NFPA 101 - 13.2.1 & 7.5.1.1
b. Exits shall be arranged so the total length of travel distance from any point to
reach an exit shall not exceed 200 feet. (NFPA 101 - 13.2.6))
c. The main center walk way aisle shall be a minimum of 36 inches of clear width.
(NFPA 101 - 13.2.1 & 7.3.4.1)
Portable fire extinguishers:
Portable fire extinguishers are required in all tents. (NFPA 101 - 11.11.5) Arrangements should be made with the vendor supplying the tent(s) or a local fire extinguisher vendor for supplying portable fire extinguishers. No display or exhibit shall be installed or operated to interfere in any way with access to fire extinguishers.
a. The minimum rating for portable fire extinguishers is 3A:40B:C. Portable fire extinguisher sizes of 51b. or 101b. ABC rating will typically meet the rating requirement. (NFPA 10 - Table 5.2.1)
b. The maximum travel distance to portable fire extinguishers shall not exceed 75 feet. (NFPA 10 - Table 5.2.1)
c. A minimum of 1 portable fire extinguisher is required in tents not exceeding 75 feet in length. Tents exceeding 75 feet in length shall have a minimum of 2 portable fire extinguishers. (NFPA 10 - Table 5.2.1)
d. Portable fire extinguishers shall not be obstructed from view or access. (NFPA 10 - 1.5.6)
e. Brackets for the portable fire extinguishers shall be securely mounted so the top of the fire extinguisher is not more than 5 feet from the floor (ground). (NFPA 10 - 1.5.10)
f. Portable fire extinguishers shall have a current inspection tag from a licensed fire extinguisher vendor.
Electrical:
Electrical shall meet the requirements of NFPA 70, National Electrical Code.
a. Typical electrical wiring or cord requirements:
1. In good working condition.
2. Suitable for outside use.
3. Protected by Ground Fault Circuit Interrupter (FGCI) 4. Of sufficient size to handle electrical load. 5. Protected from pedestrian foot traffic.
Crowd Managers:
There shall be a minimum of 1 Crowd Manager per 250 occupants. The crowd managers are present to assist with crowd control. When tents are filled to capacity or become too crowded for free movement, the crowd managers shall restrict entry until the crowd diminishes. The crowd managers shall also have knowledge of the locations of exits, the locations of portable fire extinguishers, and trained how to direct occupants in the event of an emergency. (NFPA 101 - 13.7.6).
Emergency Services:
Vehicle Access Fire Lane and Height Requirements: Austin Fire Department:
a. Fire lane and height requirements shall be maintained at all times.
b. The minimum width for emergency vehicle access is 15 feet for one way traffic.
c. The minimum width for emergency vehicle access is 25 feet for two way traffic.
d. The minimum height clearance for overhead banners and such is 13 feet, 6
inches.
Should you have any questions, please contact Deputy State Fire Marshal John Nichols at (512) 463-5479 or e-mail address john.nichols@tdi.state.tx.us